Rockwell Automation Publication 1609-QS002A-EN-P - May 2014

27

Appendix B

EtherNet/IP Parameters

19

Required

Get

V

Input Line Value

STRUCT of:

The current input values for up to InputNumLines

Frequency

INT

Line frequency to the UPS system in
1/10 Hz

Voltage 1

INT

Line voltage of the UPS system in
1/10 V

20

Required

Get

V

OutputSource

INT

The present source of output power. The
enumeration none(7) indicates that there is no
source of output power (and therefore no output
power), for example, the system has opened the
output breaker

normal(0),
battery(1),
bypass(2),
reducing(3),
boosting(4),
manualBypass(5),
other(6),
none(7)

21

Required

Get

V

OutputFrequency

INT

The present output frequency in
1/10 Hz

22

Required

Get

V

OutputNumLines

INT

The number of output lines utilized in this device

23

Required

Get

V

Output Line Status

Array of
STRUCT of:

The Output Line values for up to OutputNumLines

Voltage

INT

line voltage of the UPS system in
1/10V

Current

INT

line current of the UPS system in
1/10 A

Power

INT

line eal power of the UPS system in watts

Load

INT

line load expressed in percent of rated capacity

24

Required

Get

V

BatteryCondition

INT

The indication of the capacity remaining in the
UPS system's batteries when AC normal.

good(0),
weak(1),
replace(2)

25

Required

Get

V

BatteryStatus

INT

The indication of the capacity remaining in the
UPS system's batteries when AC failed. A value
of ok indicates that the remaining run-time is
greater than upsConfigLowBattTime. A value of
low indicates that the remaining battery run-time
is less than or equal to upsConfigLowBattTime.
A value of depleted indicates that the UPS will be
unable to sustain the present load when and if the
utility power is lost (including the possibility that
the utility power is currently absent and the UPS is
unable to sustain the output).

ok(0),
low(1),
depleted(2)

26

Required

Get

V

BatteryCharge

INT

floating(0),
charging(1),
resting(2),
discharging(3)

27

Required

Get

V

BatteryEstimatedTime

INT

Estimated time from backup to low battery
shutdown

28

Required

Get

V

BatteryVoltage

INT

The magnitude of the present battery voltage in
1/10 V

29

Required

Get

V

BatteryCapacity

INT

An estimate of the battery charge remaining
expressed as a percent of full charge

30

Required

Get

V

Battery Temperature

INT

The ambient temperature at or near the UPS
Battery casing

°C

31

Required

Get/Set

V

TestType

INT

Perform the UPS Test procedure

abort(0),
generalTest(1),
batteryTest(2),
testFor10sec(3),
testUntilBattlow(4)

UPS Object (0x377)
Attribute ID Need

Access Rule

NV

Name

Data Type

Description of Attribute

Semantics of value