18 Compact 1769-OF4CI Isolated Analog Output Module

Rockwell Automation Publication 1769-IN075B-EN-P - August 2010

Input Data File

For each module, slot x, input data file words 2…5 contain the state of the
module’s output data (output data echo) file words 0…3. During normal
operation, these input words represent the analog values that the outputs are
directed to by the control program.

S = General status (over-range, under-range, or low/high clamp
exceeded).

H = Output held bit.

U = Under-range (or low-clamp exceeded) alarm.

O = Over-range (or high-clamp exceeded) alarm.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

S3

S2

S1

S0

1

H3

U3

O3

H2

U2

O2

H1

U1

O1

H0

U0

O0

2

Channel 0 Data Value

3

Channel 1 Data Value

4

Channel 2 Data Value

5

Channel 3 Data Value

IMPORTANT

The output module’s input data file reflects the analog output
data echo of the module, not necessarily the electrical state of
the output terminals. It does not reflect shorted or open outputs.