North american hazardous location approval – Rockwell Automation 1769-OF4CI CompactLogix 1769-OF4CI Module User Manual

Page 3

Advertising
background image

Compact 1769-OF4CI Isolated Analog Output Module 3

Rockwell Automation Publication 1769-IN075B-EN-P - August 2010

North American Hazardous Location Approval

The following information applies
when operating this equipment in
hazardous locations.

Informations sur l’utilisation de cet
équipement en environnements
dangereux.

Products marked "CL I, DIV 2, GP A, B, C, D" are
suitable for use in Class I Division 2 Groups A, B, C,
D, Hazardous Locations and nonhazardous
locations only. Each product is supplied with
markings on the rating nameplate indicating the
hazardous location temperature code. When
combining products within a system, the most
adverse temperature code (lowest "T" number) may
be used to help determine the overall temperature
code of the system. Combinations of equipment in
your system are subject to investigation by the
local Authority Having Jurisdiction at the time of
installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements
de Classe I Division 2 Groupes A, B, C, D dangereux et
non dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés
dans un système, le code de température le plus
défavorable (code de température le plus faible) peut
être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements
dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de
l'installation.

WARNING:
Explosion Hazard -

• Do not disconnect equipment

unless power has been removed
or the area is known to be
nonhazardous.

• Do not disconnect connections to

this equipment unless power has
been removed or the area is
known to be nonhazardous.
Secure any external connections
that mate to this equipment by
using screws, sliding latches,
threaded connectors, or other
means provided with this product.

• Substitution of components may

impair suitability for Class I,
Division 2.

• If this product contains batteries,

they must only be changed in an
area known to be nonhazardous.

AVERTISSEMENT:
Risque d’Explosion –

• Couper le courant ou s'assurer que

l'environnement est classé non
dangereux avant de débrancher
l'équipement.

• Couper le courant ou s'assurer que

l'environnement est classé non
dangereux avant de débrancher les
connecteurs. Fixer tous les
connecteurs externes reliés à cet
équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou
autres moyens fournis avec ce
produit.

• La substitution de composants peut

rendre cet équipement inadapté à
une utilisation en environnement de
Classe I, Division 2.

• S'assurer que l'environnement est

classé non dangereux avant de
changer les piles.

Advertising