Configuration data file – Rockwell Automation 1769-OF4CI CompactLogix 1769-OF4CI Module User Manual

Page 19

Advertising
background image

Compact 1769-OF4CI Isolated Analog Output Module 19

Rockwell Automation Publication 1769-IN075B-EN-P - August 2010

Configuration Data File

The manipulation of the bits from this file is normally done with programming
software (for example, RSLogix 500 software or RSNetworx for DeviceNet
software) during initial configuration of the system. In that case, graphical
screens are provided by the programmer to simplify configuration.

However, some systems, like the 1769-ADN DeviceNet Adapter, also allow the
bits to be altered as part of the control program, using communication rungs. In
that case, it is necessary to understand the bit arrangement. The channel
configuration words, the first two words of each eight word group, are described
on page

20

. Refer to your module’s user manual for additional details.

Word

Description

Word

Description

0

Channel 0 Configuration Word 0

16

Channel 2 Configuration Word 0

1

Channel 0 Configuration Word 1

17

Channel 2 Configuration Word 1

2

Channel 0 Fault Value Word

18

Channel 2 Fault Value Word

3

Channel 0 Program Idle Mode
Word

19

Channel 2 Program Idle Mode
Word

4

Channel 0 Low Clamp

20

Channel 2 Low Clamp

5

Channel 0 High Clamp

21

Channel 2 High Clamp

6

Channel 0 Ramp Rate

22

Channel 2 Ramp Rate

7

Channel 0 Spare

23

Channel 2 Spare

8

Channel 1 Configuration Word 0

24

Channel 3 Configuration Word 0

9

Channel 1 Configuration Word 1

25

Channel 3 Configuration Word 1

10

Channel 1 Fault Value Word

26

Channel 3 Fault Value Word

11

Channel 1 Program Idle Mode
Word

27

Channel 3 Program Idle Mode
Word

12

Channel 1 Low Clamp

28

Channel 3 Low Clamp

13

Channel 1 High Clamp

29

Channel 3 High Clamp

14

Channel 1 Ramp Rate

30

Channel 3 Ramp Rate

15

Channel 1 Spare

31

Channel 3 Spare

Advertising