10 ArmorPoint ControlNet Adapter, Series A

Specifications

Following are specifications for the 1738 ArmorPoint ControlNet
adapter.

ArmorPoint Control Adapter - 1738-ACNR

Expansion I/O Capacity

• Maximum of 63 modules
• Maximum of 5 Rack Optimized connections (for digital modules

only)

• Maximum of 25 Direct connections
• 1738-ACNR backplane current output = 1.0A maximum. See

the list below for backplane current consumption for each
ArmorPoint I/O catalog number and the current consumption
for each of the ArmorPoint modules connected to the
1738-ACNR. Verify that it is below 1.0A.

• Backplane current can be extended beyond 1.0A with a

1738-EP24DC Backplane Extension Power Supply. The
1738-EP24DC can supply up to an additional 1.3A of backplane
current.

• Multiple 1738-EP24DC modules can be used to reach the

maximum of 63 modules.


Cat. No.

PointBus Current Requirements

1738-IB2M12 75mA

1738-IB4xxx

75mA

1738-IB8xxx 75mA

1738-IV4xxx 75mA

1738-OB2EM12

75mA

1738-OB2EPM12

75mA

1738-OB4Exxx

75mA

1738-OB8Exxx

75mA

1738-OV4EM12

75mA

1738-OW4xxx 90mA

1738-IE2CM12 75mA

1738-OE2CM12

75mA

1738-IE2VM12 75mA

1738-OE2VM12 75mA

1738-IA2xxx 75mA

1738-OA2xxx 75mA

1738-IJM23

160mA

1738-SSIM23

110mA

1738-IR2M12 220mA

1738-IT2IM12 175mA

1738-VHSC24M23 180mA

1738-232ASCM12

75mA

1738-485ASCM12

75mA

ControlNet Communication Rate

5Mbits/s (fixed value)