Troubleshoot with the indicators – Rockwell Automation 1738-ACNR ArmorPoint ControlNet Adapter, Series A  User Manual

Page 8

Advertising
background image

Publication 1738-IN016B-EN-E - March 2005

8 ArmorPoint ControlNet Adapter, Series A

Troubleshoot with

the Indicators

ControlNet B

1738-ACNR

ControlNet A

X10

X1

Adapter
Status

PontBus
Status

ControlNet A
Status

ControlNet B
Status

System
Power

Adapter
Power

PWR

Adapter Status Indicator

PointBus Status Indicator

ControlNet A Status Indicator

System Power Indicator

Adapter Power Indicator

43792

ControlNet B Status Indicator

Indication

Indication

Probable Cause

Adapter Status

Off

No power applied to device.

Alternating Red/Green

LED powerup test (module self-test).

Flashing Red

Recoverable fault has occurred:

- Firmware (NVS) update

- MAC ID changed

- CPU load exceeded.

Solid Red

Unrecoverable fault has occurred:

- self test failure (checksum failure at powerup, ramtest failure)

at powerup

- firmware fatal error.

Flashing Green

Waiting for connection or ControlNet cable break.

Solid Green

Module is operating correctly (normal mode).