Publication 1738-IN016B-EN-E - March 2005

11 ArmorPoint ControlNet Adapter, Series A

Power Supply Specifications

Power Supply

Note: In order to comply with CE Low Voltage

Directives (LVD), you must use either a NEC Class

2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage
(PELV) power supply to power this adapter. A SELV supply cannot
exceed 30V rms, 42.4V peak or 60V dc under normal conditions and
under single fault conditions. A PELV supply has the same rating and is
connected to protected earth.

Input Voltage Rating

24V dc

10-28.8V dc range

Inrush Current

6A maximum for 10ms

Field Side Power Requirements, Maximum

24V dc (+20% = 28.8V dc) @ 425 mA

Interruption

Output voltage will stay within specifications when input drops out for
10ms at 10V with maximum load

General Specifications
LED Indicators

1 green/red Adapter status

2 green/red ControlNet status

1 green/red PointBus status

1 green System Power (PointBus 5V power)

1 green Adapter Power (24V from field supply)

Power Consumption, Maximum

10.2W @ 28.8V dc

Power Dissipation, Maximum

5.0W @ 28.8V dc

Thermal Dissipation, Maximum

16.9 BTU/hr. @ 28.8V dc

PointBus Output Current, Maximum

1A @ 5V dc +5% (4.75-5.25)

Input Overvoltage Protection

Reserve polarity protected

Isolation Voltage

(continuous-voltage withstand rating)

50V rms

Tested at 1250V ac for 60s

Field Power Bus

Nominal Voltage

Supply Voltage

Supply Current


24V dc

10-28.8V dc range

10A maximum

Dimensions Inches (Millimeters)

4.41H x 2.83W x 2.56D (112H x 72W x 65D)

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20 to 60°C (-4 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):

5-95% non-condensing

Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

Operating 30g

Non-operating 50g

Vibration

IEC60068-2-6 (Test Fc, Operating):

5g @ 10-500Hz

ESD Immunity

IEC 61000-4-2:

6kV contact discharges

8kV air discharges