Publication 1738-IN016B-EN-E - March 2005

ArmorPoint ControlNet Adapter, Series A 9

PointBus Status

Off

Device is not powered - check module status indicator.

Alternating Red/Green

LED powerup test.

Flashing Red

Recoverable fault has occurred:

- at power up the number of expected modules does not

equal the number of modules present

- a module is missing

- node fault (I/O connection timeout).

Red

Unrecoverable fault has occurred:

- the adapter is bus off

- the adapter has failed its dup_MAC_ID check.

Flashing Green

Adapter is on line with no connections established:

- adapter chassis size has not been configured

- controller in program/Idle mode

- ControlNet cable break.

Green

Adapter is on line with connections established (normal
operation, in run mode).

ControlNet A/B
Status (Viewed
together)

Both Steady Off

Reset, no power or entire network interface deactivated.

Alternating Red/Green

Self test mode.

Alternating Red/Off

Bad/invalid node configuration (such as dup_MAC_ID).

Both Steady Red

Failed link interface.

ControlNet A/B
Status (Viewed
individually)

Steady Off

Channel disabled or channel not supported.

Flashing Red/Green

Invalid link configuration.

Flashing Red/Off

Severe link error - link fault or no MAC frames received.

Flashing Green/Off

Temporary channel error or listen-only.

Steady Green

Normal operation - MAC frames are being received without
detected error.

System Power

Off

Not active - Field power is off or dc-dc converter problem.

Green

Power on - dc-dc converter active (5V).

Adapter Power

Off

Not active - Field power is off.

Green

Power on - 24V present.

Indication

Indication

Probable Cause