Indicator

State

Description

Module
status

Off

No power applied to device

Solid green

Device operating normally

Flashing

red/green

Module self-test

Flashing red

Recoverable fault.

Complete firmware update, verify address switches.

Solid red

Unrecoverable fault, may require device replacement

Network
status

Off

Device is not on-line

- Device has not completed dup_MAC_id test.

- Device not powered - check module status indicator

Flashing green

Device is on-line but has no CIP connections in the
established state.

Solid green

Device on-line and has CIP connections in the established
state.

Flashing red

One or more CIP connections in timed-out state.

Check for I/O module failure and controller operation.

Solid red

Duplicate IP address detected.

Verify IP address setting and correct, as needed.

Flashing
red/green

Module self-test