POINT I/O 2 Port Ethernet Adapter 19

Publication

1734-IN040B-EN-P - December 2009

POINTBus
status

Off

Device is not online.

Device has not completed Dup_MAC_ID test.

Device not powered - check module status indicator.

Flashing green

Device is online but has no connections in the established
state.

Firmware (NVS) update in progress.

Solid green

Adapter online with connections established.

Flashing red

Recoverable fault occurred:

• At cycle power, the number of expected modules

does not equal the number of modules present.

• A module is missing.

• Node fault (I/O connection timeout) occurred.

Solid red

Unrecoverable fault occurred - the adapter is bus off.

Flashing
red/green

LED powerup test is in progress.

System
power

Off

Not active. Adapter power is off or there is a DC-DC
converter problem.

Solid green

System power is on. DC-DC converter output is active (5V).

Field power Off

Not active. Adapter power is off.

Solid green

Power is on. 24V input is present.

Indicator

State

Description