European Hazardous Location Approval

European Zone 2 Certification (The following applies when the product bears the
Ex Marking)

This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 94/9/EC and has been found to comply with the Essential Health
and Safety Requirements relating to the design and construction of Category 3 equipment
intended for use in potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 60079-15 and EN 60079-0.

WARNING

Observe the following additional Zone 2 certification requirements.

• This equipment is not resistant to sunlight or other sources of UV

radiation.

• This equipment must be installed in an enclosure providing at least

IP54 protection when applied in Zone 2 environments.

• This equipment shall be used within its specified ratings defined by

Allen-Bradley.

• Provision shall be made to prevent the rated voltage from being

exceeded by transient disturbances of more than 40% when applied
in Zone 2 environments.

• Secure any external connections that mate to this equipment by

using screws, sliding latches, threaded connectors, or other means
provided with this product.

• Do not disconnect equipment unless power has been removed or the

area is known to be nonhazardous.