1734-IN040B-EN-P - December 2009

Surge transient
immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports

±2 kV line-earth(CM) on communications ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications

Certification (when

product is marked)

(1)

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and

Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous

Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with:

EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements

II 3 G Ex nA nL IIC T4 X

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications

(1)

See the Product Certification link at

http://www.ab.com

for Declaration of Conformity, Certificates,

and other certification details.

Environmental

Attribute

Value

Advertising