Publication 1771-IN014B-EN-P - September 2001

DeviceNet Scanner Module Catalog Number 1771-SDN/C 11

Note: The scanner module consumes/produces 8 bits of discrete
output/input for the processor connection. Therefore, the scanner
module cannot be placed next to a 16-point module when using
1-slot addressing.

3. Using a ball point pen or similar pointed object, adjust switches

7 and 8 to your desired chassis addressing mode. Slide the
switches up to denote an on or “1” position. Slide the switches
down to denote an off or “0” position. Make sure switches 1
through 4 and 6 in the switchbank labeled “Configuration”
always remain in the off or “0” position. For Series C
functionality, make sure switch 5 is in the on or “1”
position.

Set Node Address
Switches for Channels
1 and 2

For more information about addressing, refer to your PLC processor
system level installation manual and design manual.

To set the scanner DeviceNet node address:

1. Locate the switchbank labeled “Channel 1”, on the left side of

the module.

2. Use the following table to determine the node address you want

to set for the module on Channel 1, and note your choice. The
address range is 0 to 63.

3. Using a ball point pen or similar object, adjust switches 3

through 8 to your desired node address settings. Slide the
switches up to denote an on or “1” position. Slide the switches
down to denote an off or “0” position.

4. Using a ball point pen or similar object, adjust switches 3

through 8 to your desired node address settings. Slide the
switches up to denote an on or “1” position. Slide the switches
down to denote an off or “0” position.

I/O Chassis Addressing Mode

Mode

Switch Position

Note Your

Mode

7

8

2-slot

0

0

1-slot

0

1

1/2-slot

1

0

Not allowed

1

1

ATTENTION

!

ATTENTION

!

The I/O chassis address setting must match
the chassis addressing mode setting for the
1771 chassis. If the switches do not match,
data will be lost in the data transfer between
the PLC-5 processor and the scanner module.

Node Address

Channel 1

20276