32 DeviceNet Scanner Module Catalog Number 1771-SDN/C

Depending on the network load, the scanner could take a few
seconds to complete the request. When a response is loaded, bit 15 of
the module status register is set to 1. The program may have to poll
the scanner module a number of times before the scanner returns
a Response Transaction Block.

The scanner module recognizes I/O data and control as higher
priorities over explicit messaging on DeviceNet.

Message lengths and slave device types impact transaction message
completion times. If the processor has queued multiple Explicit
Message Transactions to the scanner module for multiple slave
devices, the transactions with the slaves may not complete in the
order in which the requests were received. The slave responses are
queued to the 64 word Block Transfer Read in the order in which they
are received. As response transaction blocks are uploaded, the
processor’s program matches the responses to the requests using
the TXID field.

Request

Transaction

Block

Response

Transaction

Block

Ladder Scans

Process Requests
and Responses

Request

Transaction

Blocks

Response

Transaction

Blocks

Scanner

Response

Queue

Scanner
Request

Queue

Execute

Done or

Error-detected

BTR

BTW

Processor

Scanner Module

DeviceNet

Explicit Message

Requests and

Responses

DeviceNet Network

Slave

Device