DeviceNet Scanner Module Catalog Number 1771-SDN/C 39

Specifications

Module Location

1771-A1B through -A4B or later I/O chassis

Module Defaults

Node Address – 63
Baud Rate – 125 Kbits/s

Power Consumption
- Backplane Current
- DeviceNet

1

5Vdc, 0.8A
24Vdc, 50mA per channel Class 2

Isolation Voltage

Optical Isolation between backplane and DeviceNet channel,
tested to withstand 500Vac for 60 seconds
1 Megohm resistor from DeviceNet channel to chassis

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0-60

o

C (32–140

o

F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bc, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
–40 to 85

o

C (–40 to 185

o

F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
5–95% non condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
2g @10–500Hz

Shock

IEC60068-2-27:1987, Test Ea (Unpackaged shock, ES#002)
Operating - 30g
Non-operating - 50g

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
4kV contact discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m, 3V/m Broadcast Bands, with 1kHz sine-wave 80% AM
from 30MHz to 1000Mhz

EFT/B Immunity

IEC 61000-4-4:
+2kV at 5kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:
+2kV line-earth(CM)
on signal ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz
to 30MHz

Enclosure Type Rating

None (open style)

Wiring
- Type
- Category

2

1771-CD
2

10-pin Linear Plug
- Torque
- Catalog Number

5-7 pound-inches
1787-PLUG10R

Dimesions (HxWxD)

270 x 30 x 170mm (10.6 x 1.2 x 6.7 inches)

Weight

0.9kg (1.9lb)

1

To remain compliant with UL/CSA certification, the DeviceNet power supply must meet NEC Class 2

requirements.

2

Use this conductor category information for planning conductor routing as described in publication

1770-4.1,

Industrial Automation Wiring and Grounding Guidelines.