Rockwell Automation 1771-SDN DeviceNet Scanner Module Installation Instructions User Manual

Page 15

Advertising
background image

Publication 1771-IN014B-EN-P - September 2001

DeviceNet Scanner Module Catalog Number 1771-SDN/C 15

1. Connect the DeviceNet drop line to the linear plug, by matching

the wire insulation colors to the colors shown on the label:

2. Locate the DeviceNet

Port 1 connector for Channel 1 on the

front of the module.

3. Insert the linear plug into the five-pin header for

Channel 1.

4. Repeat steps 1–3 for Channel 2, if necessary.

Module installation is complete. To operate the module,
you must program the PLC processor to communicate with it. In the
following two sections, we describe how your module communicates
with the PLC-5 processor and how to program your processor.

20298

Front of Scanner Module

+24V RED

Can_H WHITE

Drain/Shield
Can_L BLUE
+24V Return BLACK

Module label shows
wiring color scheme:

Ten-pin
Linear
Plug

DeviceNet
Drop Line

Black

Blue

White

Red

Bare (shield)

20298

Five-Pin
Header

DeviceNet Port 1
for Channel 1

DeviceNet
Drop Line

Black

Blue

White

Red

Bare (shield)

WARNING

!

WARNING

!

If you connect or disconnect the DeviceNet cable
with power applied to this module or any device on
the network, an electrical arc can occur. This could
cause an explosion in hazardous location
installations. Be sure that power is removed or the
area is nonhazardous before proceeding.