62 Using the Module

I.EventOverflow

Per point

Set for an input when the module either:

Does not timestamp a transition on the input – The module has Timestamp
Latching enabled and a similar transition has already been timestamped on
this input but has not been cleared via the O.EventAck and O.NewDataAck
output tags (see

page 82

).

or

Overwrites previously-recorded timestamp data for the input – The module
has Timestamp Latching disabled and multiple transitions occur on the input.
In this case, timestamp data from new transitions are recorded before
previously-recorded transitions were cleared from the input via the
O.EventAck and O.NewDataAck output tags (see

page 82

).

This tag only clears when the controller acknowledges the new data or all events on
the module are reset. For more information on clearing timestamp data, see

page 64

.

I.EventNumber.x

Modulewide

Running count of the timestamped transitions; this tag increments by one with each
new transition that the module timestamps.

This value is cleared if the power is cycled and rolls over 1 instead of 0.

I.LocalClockOffset

Modulewide

The offset from the local clock to the system time. This value is useful for detecting
steps in time.

This value updates when a PTP update is received.

I.OffsetTimeStamp

Modulewide

The time when the PTP message was received to cause the Local Clock Offset to
update.

This value is initially zero. The first timestamp occurs when the module synchronizes
with the Grandmaster clock.

I.GrandMasterClockID

Modulewide

The I.D. number of the Grandmaster clock that the module is synchronized to.

I.Timestamp[16].OffOn[2] Per point

Timestamp value for an input’s OFF to ON transition. This tag is a 16 x 2 32-bit array.
There is a 64-bit timestamp per point.

This value is cleared after the data has been acknowledged via the O.EventAck and
O.NewData tags. For more information on clearing timestamp data, see

page 64

.

I.Timestamp[16].OnOff[2] Per point

Timestamp value for an input’s ON to OFF transition. This tag is a 16 x 2 32-bit array.
There is a 64-bit timestamp per point.

This value is cleared after the data has been acknowledged via the O.EventAck and
O.NewData tags. For more information on clearing timestamp data, see

page 64

.

I.SyncedToMaster

Modulewide

Indicates if the module is synchronized with a master clock.

1 = Synchronized
0 = Not synchronized

Tag Name

Set on a Per Point or
Modulewide Basis

Description