Ethernet connections, Duplicate ip address detection – Rockwell Automation 1732E-IB16M12SOEDR EtherNet/IP ArmorBlock supporting Sequence of Events User Manual

Page 99

Advertising
background image

Publication 1732E-UM002A-EN-P - March 2010

Connect to Networks via Ethernet Interface 91

Ethernet Connections

TCP/IP is the mechanism used to transport Ethernet messages. On top of
TCP, the Ethernet/IP protocol is required to establish sessions and to send
MSG commands. Connections can be initiated by either a client program
(RSLinx application) or a processor.

The client program or processor must first establish a connection to the
ArmorBlock module to enable the ArmorBlock module to receive solicited
messages from a client program or processor.

In order to exchange I/O data with another device on Ethernet, that device
must first originate a connection with the ArmorBlock via TCP/IP. Once an
IO connection is established via TCP/IP the IO data is exchanged via
UDP/IP.

Duplicate IP address
Detection

The ArmorBlock module firmware supports duplicate IP address detection.

When you change the IP address or connect one of the modules to an
EtherNet/IP network, the module checks to make sure that the IP address
assigned to this device does not match the address of any other network
device. The module will periodically check for a duplicate IP address on the
network. If the module determines that there is a conflict (another device on
the network with a matching IP address), the Network Status Indicator
becomes solid red.

To correct this conflict, the IP address of one of the modules will need to
changed. If you decide to change the IP address of the ArmorBlock then,
assign a unique IP address to the module then cycle power to the module.

If you decide to change the IP address of the other module, remove the device
with the incorrect IP address or correct its conflict. To get the ArmorBlock
out of conflict mode, cycle power to the module or disconnect its Ethernet
cables and reconnect the cables. If you choose to disconnect the Ethernet
cables to correct this conflict you will need to disconnect both Ethernet cables
from two port Ethernet modules at the same time.

Configure Ethernet
Communications on the
ArmorBlock module

There are five ways to configure ArmorBlock module Ethernet
communications.

via a DHCP request at module powerup

manually setting the configuration parameters using RSLogix 5000
software

manually setting the configuration parameters using RSLinx software

manually configuring the network settings using the embedded web
server

Advertising