Rockwell Automation 1732E-IB16M12SOEDR EtherNet/IP ArmorBlock supporting Sequence of Events User Manual

Page 95

Advertising
background image

Publication 1732E-UM002A-EN-P - March 2010

1732E EtherNet/IP ArmorBlock Supporting Sequence of Events Data Tables 87

Configuration Assembly Instance 110

16 Input / Status / CIP Sync

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Reserved

CRN

1

Reserved

2

Reserved

3

Reserved

4

Group 0 Input OFF_ON Delay Filter (Low Byte)

5

Group 0 Input OFF_ON Delay Filter (High Byte)

6

Group 0 Input ON_OFF Delay Filter (Low Byte)

7

Group 0 Input ON_OFF Delay Filter (High Byte)

8

Enable IN
OW 7

Enable IN
OW 6

Enable IN
OW 5

Enable IN
OW 4

Enable IN
OW 3

Enable IN
OW 2

Enable IN
OW 1

Enable IN
OW 0

9

Master Sync
Enable

Latch
Events

10

Capture
OffOn 7

Capture
OffOn 6

Capture
OffOn 5

Capture
OffOn 4

Capture
OffOn 3

Capture
OffOn 2

Capture
OffOn 1

Capture
OffOn 0

11

Capture
OffOn 15

Capture
OffOn 14

Capture
OffOn 13

Capture
OffOn 12

Capture
OffOn 11

Capture
OffOn 10

Capture
OffOn 9

Capture
OffOn 8

12

Capture
OnOff 7

Capture
OnOff 6

Capture
OnOff 5

Capture
OnOff 4

Capture
OnOff 3

Capture
OnOff 2

Capture
OnOff 1

Capture
OnOff 0

13

Capture
OnOff 15

Capture
OnOff 14

Capture
OnOff 13

Capture
OnOff 12

Capture
OnOff 11

Capture
OnOff 10

Capture
OnOff 9

Capture
OnOff 8

Where

CRN = Configuration Revision Number, Value is 0 after power-on reset and after completely closing the connection. Value is
1 when the module is configured. Once a module is configured, the only way to change its configuration is to close the
connections to it or use the override value of 0.

Enable IN OW x = Enable Input Open Wire x
1 = Enable; 0 = Off

LatchEvents: When set, latches events which means that an event will not be overwritten until acknowledged. For example,
this means that an input’s sequence of events of Off, On, Off, On will cause the first Off to On transition to be recorded, and
the final Off to On transition to be ignored. All subsequent transitions on that point will be ignored until
acknowledged/reset. If the bit is not set, the new Off to On transition will overwrite the first Off to On transition event
immediately, even if the controller has yet to extract that data.

MasterSyncEnable: This is a PTP enable bit which will indicate if the module is expected to sync to a master clock. If not
enabled (0), then the module Status Indicator does not flash green if it is not synchronized to a master clock. Disabling the
bit does not prevent the module from synchronizing to a master clock.

CaptureOffOn: Enables capturing Off to On events on a per point basis. If cleared, that point will not record Off to On events.
This is useful for not reporting events that are not necessary.

CaptureOnOff: Enables capturing On to Off events on a per point basis. If cleared, that point will not record On to Off events.
This is useful for not reporting events that are not necessary.

Input Filter values = 0, 1000, 2000, 4000, 8000 or 16000 µs.