1732E EtherNet/IP ArmorBlock Supporting Sequence of Events Data Tables 85

In order to acknowledge receipt of an event the user must transition the
corresponding NewDataAck bit from 0 to 1 and set the EventAck to indicate
whether to acknowledge the Off-On or On-Off transition for the input. the
NewDataAck bits and EventAck are in consumed assembly 139.

Timestamps are zero at power-up and after a timestamp is acknowledged. The
time base and epoch of the timestamps are determined by the grandmaster
clock of the system.

272-279

IN 14 On-Off Time Stamp (64 bit)

280-287

IN 15 Off-On Time Stamp (64 bit)

288-295

IN 15 On-Off Time Stamp (64 bit)

296

Reserved

Synced to
Master

Where: INOW = Input Open Wire

INSC = Input Short Circuit

NewData = New data, has been detected upon that input and an unread event is queued for that point.

EventOV = Set whenever the module begins to lose events for that input pint. Events may be lost when new events are either ignored or
overwriting existing events which have yet to be acknowledged.

EventNumber = Running count of events which increments by one each new event. Allows the controller to check for a new event easily by
comparing this number to the last retrieved event. If the EventNumber reaches its maximum value and rolls over it rolls over to 1, not 0.

Inx Off-On Time Stamp = Timestamp corresponding to when an event was recorded at one of the module’s inputs when the input
transitioned from Off to On.

Inx On-Off Time Stamp = Timestamp corresponding to when an event was recorded at one of the module’s inputs when the input
transitioned from On to Off.

Local Clock Offset = The offset from the local clock to the system time. This value is useful for detecting steps in time. This value will
update when a PTP update is received.

Offset Time Stamp = The time when the PTP message was received that caused the Local Clock Offset to update. This value is initially zero
and the first timestamp occurs when the module synchronizes with the master clock.

Grandmaster Clock ID = The I. D. number of the Grandmaster clock the module is synchronized to.

Synced to Master = 1 indicates the module is synchronized with a master clock. 0 indicates it is not.

Produced Assembly Instance 118