12 ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A

Publication

1738-IN028B-EN-E - February 2010

Red

Unrecoverable fault has occurred:

- self-test failure (Flash checksum
failure at power up, ramtest failure
or EEPROM checksum failure at cycle
power).

- firmware fatal error.

Replace device.

Network Activity

Status

Description

Recommended action

Off

No link established with Port 1 or
Port 2.

Verify network cabling, and
correct, as needed.

Green

- Link established with Port 1 and/or
Port 2 at 100 Mbps.

- Link established with Port 1 and
Port 2. One port at 100 Mbps and one
port at 10 Mbps.

None.

Flashing
green

- Transmit or receive activity present
on Port 1 and/or Port 2 at 100 Mbps.

- Transmit or receive activity present
on Port 1 and/or Port 2. One port at
100 Mbps and one port at 10 Mbps.

None.

Yellow

Link established with Port 1 and/or
Port 2 at 10 Mbps.

None.

Flashing
yellow

Transmit or receive activity present
Port 1 and/or Port 2 at 10 Mbps.

None.

Adapter Status (Continued)