Rockwell Automation 1738-AENTR Armorpoint 2 Port Enet Adapter User Manual

Page 14

Advertising
background image

14 ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A

Publication

1738-IN028B-EN-E - February 2010

Adapter Power

Status

Description

Recommended action

Off

Not active; adapter power is off.

Apply adapter power.

Green

Power is on; 24V input is present.

None.

PointBus Status

Status

Description

Recommended action

Off

Device is not online.

- Device has not completed
dup_MAC_id test.

- Device not powered - check
Adapter Status indicator.

Apply power to device, wait for
dup_MAC_id to complete, and
correct, as needed.

Green

Device is online and has connections
in the established state.

None.

Flashing
green

Device is online but has no
connections in the established state.
Firmware (NVS) update in progress.

None.

Wait for the firmware update to
complete.

Flashing
red/green

LED cycle power test present.

None.

Flashing red

Communication faulted device - the
device has detected a network
access error and is in communication
faulted state.

Device has received and accepted an
Identify Communication Faulted
Request - long protocol message.

Verify that adapter is properly
installed, and reinstall, as needed.

Advertising