General

Attribute

Value

Number of modules supported,
maximum

63

Number of rack optimized
connections

5 (for digital modules only)

Number of direct connections,
maximum

20

Backplane output current,
maximum

0.8 A

The actual number of modules can vary. Add up the
requirements of the modules you want to use, for
current, to make sure they do not exceed the
amperage limit of 0.8 A for the 1738-AENTR.

Backplane current can be extended beyond 0.8 A by
using a 1738-EP24DC Backplane Extension Power
Supply. Add multiple 1738-EP24DC modules to
achieve the maximum limit of 63 modules.

Input voltage rating

24V DC nominal

10…28.8V DC range

Field side power requirements

24V DC (+20% = 28.8 V DC maximum) @ 400 mA
maximum

Inrush current, maximum

6 A for 10 ms

Interruption

Output voltage will stay within specifications when
input drops out for 10 ms at 10V with maximum load.

Input overvoltage protection

Reverse polarity protected

PointBus output current, maximum

0.8 A @ 5V DC ± 5% (4.75…5.25V DC)

Auxiliary power cable

(1)

Standard cordset (single-ended): Allen-Bradley part
number 889N-F4AFC-yF

Standard patchcord (double-ended): Allen-Bradley
part number 889N-F4AFNM-x