Wiring input devices to the nr4 module – Rockwell Automation 1746-NR4 SLC 500 RTD/Resistance Input Module/ Instructions User Manual
Page 14
14 SLC 500™ RTD/Resistance Input Module
Publication 1746-IN012B-EN-P - May 2001
Wiring Input Devices to the NR4 Module
To wire your NR4 module, follow these steps.
1. At each end of the cable, strip some casing to expose the individual wires.
2. Trim the signal wires to 5.08 cm (2 in.) lengths. Strip about 4.76 mm
(3/16 in.) of insulation away to expose the end of the wire.
3. At one end of the cable twist the drain wire and foil shield together, bend
them away from the cable, and apply shrink wrap. Then earth ground at the
shield terminal.
4. At the other end of the cable, cut the drain wire and foil shield back to the
cable and apply shrink wrap.
5. Connect the signal wires and cable shield to the NR4 terminal block and the
input.
6. Repeat steps 1 through 5 for each channel on the NR4 module.
2-Conductor Shielded Cable
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Drain Wire
Drain Wire
Foil Shield
Foil Shield
3-Conductor Shielded Cable
(See Step 4.)
(See Step 4.)
(See step 3.)