14 SLC 500™ RTD/Resistance Input Module

Publication 1746-IN012B-EN-P - May 2001

Wiring Input Devices to the NR4 Module

To wire your NR4 module, follow these steps.

1. At each end of the cable, strip some casing to expose the individual wires.

2. Trim the signal wires to 5.08 cm (2 in.) lengths. Strip about 4.76 mm

(3/16 in.) of insulation away to expose the end of the wire.

3. At one end of the cable twist the drain wire and foil shield together, bend

them away from the cable, and apply shrink wrap. Then earth ground at the
shield terminal.

4. At the other end of the cable, cut the drain wire and foil shield back to the

cable and apply shrink wrap.

5. Connect the signal wires and cable shield to the NR4 terminal block and the

input.

6. Repeat steps 1 through 5 for each channel on the NR4 module.

2-Conductor Shielded Cable

Signal Wire

Signal Wire

Signal Wire

Signal Wire

Signal Wire

Signal Wire

Signal Wire

Signal Wire

Signal Wire

Signal Wire

Drain Wire

Drain Wire

Foil Shield

Foil Shield

3-Conductor Shielded Cable

(See Step 4.)

(See Step 4.)

(See step 3.)

(See step 3.)

Advertising