SLC 500™ RTD/Resistance Input Module 23

Publication 1746-IN012B-EN-P - May 2001

IMPORTANT

Module accuracy, using 100

or 200

platinum RTDs with

0.5 mA excitation current, depends on the following criteria:

Module accuracy is ± 0.6°C after you apply power to the
module or perform an autocalibration at 25°C ambient with
module operating temperature at 25°C.

Module accuracy is ± (0.6°C + DT x 0.034°C/°C) after you
apply power to the module or perform an autocalibration at
25°C ambient with the module operating temperature
between 0° to 60°C.

where DT is the temperature difference between the

actual operating temperature of the module and 25°C
and 0.034°C/°C is the temperature drift shown in the
table on page 22 for 100

or 200

platinum RTDs.

Module accuracy is ± 1.0°C after you apply power to the
module or perform an autocalibration at 60°C ambient with
module operating temperature at 60°C.