20 SLC 500™ RTD/Resistance Input Module

Publication 1746-IN012B-EN-P - May 2001

Input Specifications

RTD Types

platinum, nickel, nickel iron, copper
(For additional information on RTD types, see page 21.)

Temperature
Scale
(Selectable)

°C or °F and 0.1°C or 0.1°F

Resistance Scale
(Selectable)

1

or 0.1

for all resistance ranges; or 0.1

or 0.01

for 150

potentiometer.

Input Step
Response

Refer to the

SLC 500™ RTD/Resistance Input Module User Manual, 1746-6.7.

Channel Turn-On
Time

Requires up to one module update time

plus one of the following:

250 Hz Filter = 388 milliseconds

60 Hz Filter = 1,300 milliseconds

50 Hz Filter = 1,540 milliseconds

10 Hz Filter = 7,300 milliseconds

Channel Turn-Off
Time

Requires up to one module update time.

Reconfiguration
Time

Requires up to one module update time

plus one of the following:

250 Hz Filter = 124 milliseconds

60 Hz Filter = 504 milliseconds

50 Hz Filter = 604 milliseconds

10 Hz Filter = 3,004 milliseconds

RTD Excitation
Current

Two current values are user-selectable:

0.5 mA - Recommended for use with higher resistance ranges for both RTDs and
direct resistance inputs (1000

RTDs and 3000

resistance input). Refer to RTD

manufacturer for recommendations. Cannot use for 10

Copper RTD.

2.0 mA - Must use for 10

Copper RTD. Recommended to use for all other

RTD and direct resistance inputs, except 1000

RTDs and 3000

resistance

input ranges are limited. Refer to RTD manufacturer for recommendations.