Specifications

Electrical Specifications

Backplane Current Consumption

50 mA at 5V dc
50 mA at 24V dc

Backplane Power Consumption

1.5W maximum (0.3 W at 5V dc, 1.2 W at 24V dc)

External Power Supply Requirements

None

Number of Channels

4 (backplane isolated)

I/O Chassis Location

Any I/O module slot except slot 0

A/D Conversion Method

Sigma-Delta Modulation

Input Filtering

Low pass digital filter with programmable notch (filter)
frequencies

Common Mode Rejection (between inputs
and chassis ground)

> 150 dB at 50 Hz (10 Hz and 50 Hz filter frequencies)
> 150 dB at 60 Hz (10 Hz and 60 Hz filter frequencies)

Normal Mode Rejection (between [+] input
and [-] input)

Greater than 100 dB at 50 Hz (10 Hz, 50 Hz filter frequencies)
Greater than 100 dB at 60 Hz (10 Hz, 60 Hz filter frequencies)

Max. common mode voltage

± 1 volt

Max. allowed permanent overload

(1)

(1)

Do not apply a voltage or current to the module.

Volts = ± 5V dc; Current = ± 5 mA

Input Filter Cut-Off Frequencies

2.62 Hz at 10 Hz filter frequency
13.1 Hz at 50 Hz filter frequency
15.72 Hz at 60 Hz filter frequency
65.5 Hz at 250 Hz filter frequency

Calibration

Module autocalibrates when a channel is enabled or when a
change is made to its input type, filter frequency or excitation
current.

Isolation (optical)

500V dc for 1 min. between inputs and chassis ground, and
between inputs and backplane

Isolation Between Inputs

None