Thermocouple/Millivolt Input Module

11

Publication 1771Ć5.64 - October 1998

Status Reported in Word 13

Design your program to monitor status bits in word 13 during
auto–calibration, and to take appropriate action depending on your
requirements. You may also want to monitor these bits while
troubleshooting with your industrial terminal. The module sets a bit
(1) to indicate it has detected one or more of the following conditions
as shown below.

Word

Bit

Condition

13

6

The EEPROM could not be written.

7

Channel(s) could not be calibrated as indicated by bits 10 through 17

respectively.

10-17

Bit 10 (channel 1) through bit 17 (channel 8) could not be calibrated.

Check field wiring arm connections and source for proper voltage.

Number of Inputs

8, all of the same type or 4 each of 2 different types

I/O Chassis Location

Any single I/O module slot

Type of Input (Selectable)

Type E, chromel/constantan

(-270 to 1000

o

C)

Type J, iron/constantan

(-210 to 1200

o

C)

Type K, chromel/alumel

(-270 to 1380

o

C)

Type R, Pt/Pt-13% Rh

(-50 to 1770

o

C)

Type T, copper/constantan

(-270 to 400

o

C)

Type S, Pt/Pt-10% Rh

(-50 to 1770

o

C)

Millivolt

(-100 to +100mV dc)

Thermocouple Linearization

IPTS-68 standard, NBS MN-125

Cold Junction Compensation

Range: 0 to 60

o

C

Accuracy: +0.5

o

C

Temperature Scale (Selectable)

o

C or

o

F

Input Resolution

1

o

C, 1

o

F, or 10uV

Input Isolation

1000V peak between inputs, between input and common, and

between input and backplane connections

Common Mode Rejection

120dB at 60Hz, up to 1000V peak

Common Mode Impedance

Greater than 10 megohms

Normal Mode Rejection

60dB at 60Hz

Input Overvoltage Protection

120V rms, continuous

Open Input Detection

Open input produces a maximum value reading in less than 10

seconds

Input Connections

18-terminal wiring arm (Cat. No. 1771-WI)

Data Format (Selectable)

4-digit BCD

2's complement binary

signed magnitude binary

Calibration

Auto-calibration (offset and gain)

Zero offset and gain adjustment for each channel via programming

terminal

Verify every six months for maintaining absolute accuracy

Processor Compatibility

Any A-B processor using the 1771 I/O structure and block transfer

Specifications continued on next page

Specifications