Thermocouple/Millivolt Input Module

8

Publication 1771Ć5.64 - October 1998

Use the following table to read data from your input module.

Dec. Bits

15 14 13 12 11 10 09 08 07 06 05 04 03

02

01

00

Description

OctalBits

17 16 15 14 13 12 11 10 07 06 05 04 03

02

01

00

Description

Word 1

Polarity Bits

EE

0

CJ

TH

CJ

TL

0 RTS OR PU

Diagnostics

EEPROM status bit - (EE) This bit is set if an error

occurs saving calibration data to nonvolatile memory. If

this bit is set at powerup, the data from the EEPROM did

not pass the checksum and no calibration values are

used.

Power up bit - (PU) Used by the

module to tell the processor that it is

alive but not yet configured. It is a key

element in the application program.

Out of range bit - (OR) This bit is sent to

tell the processor that one or more

channels are either over or under range.

Polarity bits set to indicate negative polarity: bit 10 for

channel 1 thru bit 17 for channel 8. These bits are used in

BCD and signed magnitude data formats.

Realtime sample time-out bit is set when the

module updates an input buffer with new data before

the processor has read the previous data. Monitor this

bit only if you select real time sampling.

Low cold junction temperature bit is set when

the cold junction temperature is less than 0

o

C.

High cold junction temperature bit is set when the

cold junction temperature exceeds 60

o

C.

2

Overrange bits for each channel. Bit 00

for channel 1, bit 01 for channel 2, etc.

These bits are set (1) at approximately

the input range limits shown on the right.

Underrange bits for each channel. Bit 00 for

channel 1, bit 01 for channel 2, etc. These bits

are set (1) at approximately the input range

limits shown on the right.

Data underrange and overrange bits

3

High alarm bit for each channel is set to

indicate the input has exceeded the high

limit value you entered in the

corresponding high alarm word (word 5,

7, 9, 11, 13, 15, 17, or 19): bit 10 for

channel 1 thru bit 17 for channel 8.

Low alarm bit for each channel is set to

indicate the input is less than the low limit

value you entered in the corresponding low

alarm word (word 4, 6, 8, 10, 12, 14, 16, or

18): bit 00 for channel 1 thru bit 07 for channel

8.

Low and high alarm bits

4, 5, 6, 7, 8,

9, 10, 11

Input for channel 1 through 8 respectively.

12

Cold Junction Temperature in

o

C

13

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

AutoĆCalibration Word

Calibration saved to EEPROM if bit is set

Offset calaibration complete when bit is set

Gain calibration complete when bit is set.

EEPROM fault is bit is set.

Calibration fault when bit is set.

Uncalibrated channel bits - channel not

calibrated if bit is set. Bit 10 corresponds to

channel 1, bit 11 corresponds to channel 2, etc.

For detailed configuration information,

see your Thermocouple/mV Input

Module User Manual (publication

1771Ć6.5.130).