Configure the module – Rockwell Automation 1771-IXE Installation Instructions User Manual

Page 7

Advertising
background image

Temperature scale bit, when

set, reports temperature in

o

F;

when reset, in

o

C. The module

ignores this bit for millivolt

inputs.

Input Type Enable - When set to 0 bits 00-02 define input type for all

channels.

When set to 1 bits 00-02 defines input type for channels 1-4,

and bits 03-05 defines input type for channels 5-8.

Real time sampling - Default is no

RTS.

Data format - set to

match your processor.

BCD (default)

Two's complement

binary

Signed magnitude binary

Bit 10

(12)

Bit 09

(11)

0

0

0

1

1

0

1

1

Thermocouple/Millivolt Input Module

7

Publication 1771Ć5.64 - October 1998

You must configure the module to conform to the analog device and
specific application that you have chosen. Use the configuration
information below to configure your module to your specifications.

WordDec. Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

WordOctal Bit 17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

1

Sample Time

Format

T

0

E

Input Type

Input Type

Input

Type

Bits

05 04

03

Bits

02 01 00

Millivolt

0

0

0

0

0

0

E

0

0

1

0

0

1

J

0

1

0

0

1

0

K

0

1

1

0

1

1

T

1

0

0

1

0

0

R

1

0

1

1

0

1

S

1

1

0

1

1

0

1

1

1

1

1

1

2

Not Used

Channel alarm enable bits tell the module which channel

alarm values are activated. Set bit 00 for alarm(s) in

channel 1, and set alarm(s) in words 4 (low alarm) and 5

(high alarm). Repeat the procedure for setting alarms in

channels 2 thru 8 (bits 01-07 and words 6-19

respectively).

3

High Alarms Polarity (one bit per input channel) - tell

the module the sign of the values that you enter in high

alarm words: set for negative, reset for positive. Bits

10-17 represent words 5, 7, 9, 11, 13, 15, 17 and 19 for

channels 1 thru 8, respectively.

Low Alarms Polarity (one bit per input channel) - tell

the module the sign of the values that you enter in low

alarm words: set for negative, reset for positive. Bits

00-07 represent words 4, 6, 8, 10, 12, 14, 16, and 18 for

channels 1 thru 8, respectively.

4, 6, 8, 10,

12, 14, 16, 18

Low andhigh channel alarm values that you enter via the terminal in BCD are converted automatically by the

module to its own format.

5, 7, 9, 11,

13, 15, 17, 19

Store low and high channel alarms in pairs, low alarm values in even-numbered words, high alarm values in

odd-numbered words. For example, store channel 1 low and high alarm values in words 4 and 5, respectively.

20, 21, 22,

23, 24, 25,

26, 27

Calibration words are a composite of two independent bytes for each channel. Enter calibration data in signed

magnitude binary only. The most significant bit in each byte is the sign bit; set for negative, reset for positive.

Use the high byte (bits 10-17) for offset correction, the low byte (bits 00-07) for gain correction for each channel.

Use word 20 for channel 1 thru word 27 for channel 8.

28

Auto-calibration request word- used to automatically calibrate selected channels and save the calibration

constants in EEPROM.

For detailed configuration information,

see Module Configuration" in your

Thermocouple/mV Input Module User

Manual (publication 1771Ć6.5.130).

Configure the Module