Connect wiring to the field wiring arm – Rockwell Automation 1771-IXE Installation Instructions User Manual

Page 5

Advertising
background image

Thermocouple/Millivolt Input Module

5

Publication 1771Ć5.64 - October 1998

Connect your I/O devices to the cat. no. 1771-WI wiring arm
shipped with the module.

!

ATTENTION: Remove power from the 1771 I/O
chassis backplane and field wiring arm before
removing or installing an I/O module.

Failure to remove power from the backplane or
wiring arm could cause module damage, degradation
of performance, or injury.

Failure to remove power from the backplane could
cause injury or equipment damage due to possible
unexpected operation.

Input connections for the 1771-IXE/D are shown below.

+

+

1

Do not use - reserved for cold junction

compensation within wiring arm.

Short circuit

unused pins

Channel 1

Channel 2

18

Input 1 (+ lead)

17

Input 1 (- lead)

16

Input 2 (+ lead)

15

Input 2 (- lead)

14

Input 3 (+ lead)

13

Input 3 (- lead)

12

Input 4 (+ lead)

11

Input 4 (- lead)

10

Not Used

9

Not used

8

Input 5 (+ lead)

7

Input 5 (- lead)

6

Input 6 (+ lead)

5

Input 6 (- lead)

4

Input 7 (+ lead)

3

Input 7 (- lead)

2

Input 8 (+ lead)

1

Input 8 (- lead)

Terminal Identification

Terminal

Function

Wiring Arm

Cat. No. 1771-WI

Connect positive thermocouple leads

to even-numbered terminals, negative

leads to odd-numbered terminals.
Ground cable shield to I/O chassis

mounting bolt.

18

17

16

1

15

14
13

12

11
10

9
8

7

6
5
4
3

2

10527-I

The sensor cable must be shielded. The shield must:

extend the length of the cable, but be connected only at the 1771 I/O chassis

extend up to the point of termination

Important:

The shield should extend to the termination point, exposing just enough cable to

adequately terminate the inner conductors. Use heat shrink or another suitable

insulation where the wire exits the cable jacket.

Functional

Ground

Functional

Ground

Short circuit all unused channels by

connecting a jumper wire from the

+ terminal to the - terminal

Connect Wiring to the

Field Wiring Arm