Thermocouple/Millivolt Input Module

12

Publication 1771Ć5.64 - October 1998

Backplane Power

850mA @ 5V;

Power Dissipation

4.25 Watts maximum

Thermal Dissipation

14.5 BTU/hr

Environmental Conditions

Operating Temperature:

Rate of Change:

Storage Temperature:

Relative Humidity:

0 to 60

o

C (32 to 140

o

F)

Ambient changes greater than 0.5

o

C per minute may temporarily

degrade performance during periods of change

-40 to 85

o

C (-40 to 185

o

F)

5 to 95% (without condensation)

Conductors

Wiring

Category

Use Belden 8761 shielded twisted pair for mV

Use thermocouple manufacturer recommended shielded

thermocouple wire for all thermocouple inputs.

2

Field Wiring Arm

Cat. No. 1771-WI

Keying

Between 20 and 22

Between 24 and 26

Agency Certification

(when product is marked)

CSA certified

CSA Class I, Division 2, Groups A, B, C, D certified

UL listed

CE marked for all applicable directives

User Manual

Publication 1771Ć6.5.130

Refer to publication 1770Ć4.1, Industrial Automation Wiring and Grounding Guidelines for Noise Immunity.

The accuracy of your thermocouple readings depends on:

module accuracy

lead resistance effect

accuracy of the thermocouple

Use the calibration procedure in Chapter 7 to adjust your module to
compensate for your specific environment.

Thermocouple Range Accuracy Based on Temperatures
Above 0

o

C

Column A

Column B

Thermocouple

Type

Temperature

Range

o

C

Max Error @

Calibration

Temperature (25

o

C)

1

Temperature Drift

o

C/

o

C (0-60

o

C)

or

o

F/

o

F (32-140

o

F)

E

-270 to 1000

+0.74

o

C/+1.08

o

F

+0.0400

J

-210 to 1200

+0.78

o

C/+1.10

o

F

+0.0423

K

-270 to 1380

+0.77

o

C/+1.15

o

F

+0.0640

T

-270 to 400

+0.77

o

C/+1.17

o

F

+0.0183

R

-50 to 1770

+1.50

o

C/+2.11

o

F

+0.0914

S

-50 to 1770

+1.50

o

C/+2.31

o

F

+0.0926

1

Error is specified from 0

o

C (32

o

F) to the maximum range of the thermocouple. Error

does not include thermocouple error (see appendix F). The error does include cold

junction compensation errors.

Use the calibration procedure

in Chapter 7, Module

Calibration, in your

Thermocouple/mV Input

Module User Manual

(publication 1771Ć6.5.130) to

adust your module to

compensate for your specific

environment.

Thermocouple/Millivolt

Input Module Accuracy