Thermocouple/Millivolt Input Module

14

Publication 1771Ć5.64 - October 1998

Source Impedance Compensation for Millivolt Inputs

Source resistance causes similar errors to occur with millivolt inputs.
If source resistance is less than 100 ohms, no compensation is
necessary to maintain stated accuracy. If source resistance is greater
than 100 ohms, the error can be calculated as follows:

Error (in calibration counts) =

309329 R

s

(0.22-Vin)

R

s

+ 15M ohms

-

Where R

s

= source resistance (one–way cable resistance)

V

in

= applied input voltage

When using thermocouples, Vin is the approximate thermocouple
voltage of the temperature of interest.

+

+

-

-

.22V

V

in

2V

RS

30megohms

Vo

2R

S

V

O

= V

IN

+ 2V

RS

Error = 2V

RS

Internal

Module

Circuitry

To maintain a display error of < 5uV at V

in

= OV, R

S

should be <

341 ohms. Refer to NBS NM–125 Thermocouple Reference Tables
for determining actual thermocouple voltage versus temperature
readings.

The analog input module has hardware–based high frequency filters
on all channels to reduce the effect of electrical noise on the input
signal. These are 6–pole filters, which begin rolling off at 8.0Hz.

This filtering is in addition to the software-based digital filtering
selected in the module’s BTW configuration.