Publication 1794-UM061A-EN-P - July 2006

Configure your Digital Module on an EtherNet/IP Network

99

Using RSLogix 5000 software to set the IP address

To use RSLogix 5000 software to configure the EtherNet/IP module:

1. Make sure the module in installed and powered up.

2. Connect to the controller via a serial, or other network, connection.

3. Start RSLogix 5000 software. In the Controller Organizer, select

properties for the EtherNet/IP module.

4. Select the Port Configuration tab and specify the IP address and the

other network parameters, if needed. Click Apply and then click OK.