Publication 1794-UM061A-EN-P - July 2006

32 About the FLEX I/O Diagnostic Output Module

• Channel I/O Status- This indicator displays the on/off state of each

output channel, as well as channel wiring fault conditions:

Off indicates the output channel is off with no faults.
Yellow indicates the output channel is on with no faults.
Red indicates either an output channel open or short condition.

• Module Fault Status- This indictor turns red for individual output

channel opens, shorts or module reverse power conditions.
With no fault, the module fault indicator turns off.

Module Limitations

Unused Output Channels

You must connect dummy resistors to unused output channels to mask the
diagnostic function. If these external resistors are not used, the module’s
sensing circuitry will not detect the intended voltage or current and signal a
module fault. The channel fault indicator and the module’s fault indicator will
light. The module’s open and error bits are set, thus rendering fault detection
of the remaining channels useless. The recommended value of this dummy
resistor is 10 Kohms (+10%), 1/8 W (or larger). The resistor is wired between
unused output channels and common.

Configure Your Output

Diagnostic Module

The configuration data table is shown below.

1794-OB16D Configuration Data Table

The outputs are written in Word 2. Decimal bit 00 is the first output and
decimal bit 15 is the last output.

Diagnostic status is read from Word 1:

Bit 00: Module Error Bit
Bit 01: External Power Reverse Polarity Error Bit
Bit 02: Output Short Error Bit
Bit 03: Output Open Wire Error Bit

Dec.

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Oct.

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read 1

Not used

Read Diagnostics Status

Write 2

O15

O14

O13

O12

O11

O10

O9

O8

O7

O6

O5

O4

O3

02

O1

O0

Where

O = Output
Diagnostic status;
Bit 00 = module error;
Bit 01 = external power reverse polarity error;
Bit 02 = output short error;
Bit 03 = output open wire error