52 Configure FLEX I/O Digital Modules on a DeviceNet Network

Determine the Address of

DeviceNet Data

When you add the scanner to the I/O configuration of the controller, RSLogix
5000 software automatically creates a set of tags for the input, output, and
status data of the network:

The tags for your DeviceNet data follow this format:

input data from the scanner

status data from the scanner

output data for the scanner

The scanner memory uses this format:

Which is this tag in the controller

slot

type

.Data

[element]

.bit

location

:type

.Data

[element]

.bit

= Optional

Where:

Is:

slot

slot number of the scanner

location

If you have this scanner:

Then location is:

local ControlLogix 1756-DNB

Local:slot_number_of_scanner

remote ControlLogix 1756-DNB

name_of_remote_bridge:slot_number_of_scanner

CompactLogix 1769-SDN

Local:slot_number_of_scanner

SoftLogix5800 1784-PCIDS

Local:slot_number_of_scanner

DriveLogix/FlexLogix 1788-DNBO

name of the scanner in the I/O configuration of the controller

Linking Device 1788-EN2DN or
1788-CN2DN

name of the linking device in the I/O configuration of the controller

type

If the data is:

Then type is:

input from a device

I

output to a device

O

status of the network

S

element

specific DINT (DWord, 32-bit integer) within the array

bit

specific bit within an integer