1794-ob16d diagnostic functional details – Rockwell Automation 1794-OB16D FLEX I/O Diagnostic Modules User Manual User Manual

Page 109

Advertising
background image

Publication 1794-UM061A-EN-P - July 2006

Interpret the Indicators

107

1794-OB16D Diagnostic

Functional Details

Two module indicators and four diagnostic bits report fault conditions:

the module fault indicator illuminates red and the individual faulted
channel indicator also illuminates red under output ON state open and
output OFF state short conditions.

the module fault indicator illuminates red for reverse user power
conditions.

the open bit is set for open load and wiring conditions in the output
OFF state.

the short bit is set for shorted load and wiring conditions in the output
ON state.

the reverse power bit is set for reverse polarity user power conditions.

the module fault bit is set for any open, short or reverse power
conditions detected.

The module’s diagnostic capability depends on whether the output is energized
(ON) or de-energized (OFF).

Fault

Device/Output Status

Fault

Indicators

Error Bit
Status

Conditions

Field Device Status

Output Status

Module Fault

Channel
Fault

Open

OFF

OFF

Red

Red

Open wire
& Module

No current in output terminal-
missing dummy resistor or field device,
cut output channel or Common wire

OFF

ON

OFF

Yellow

None

Can’t detect an open in the ON-state

Short

OFF

ON

Red

Red

Short & Module

Short - output to Common

OFF

OFF

OFF

OFF

None

Can’t detect a short in the OFF-state

Reverse
User Power

OFF

OFF or ON

Red

OFF

Reverse & Module

User power supply wiring is reversed