1-2 Install Your DeviceNet Adapter Module

For information on how communications occurs on the FlexArmor
system backplane, refer to Chapter 2.

DeviceNet Adapter
Components

The adapter module consists of the following major components:

diagnostic indicators

node address switch

Diagnostic Indicators

Diagnostic indicators are located on the front panel of the adapter
module. They show both normal operation and error conditions in
your remote I/O system. The indicators are:

Mod/Net status

I/O status

A complete description of the diagnostic indicators and how to use
them for troubleshooting is explained in Chapter 4.

Power Requirements

The FlexArmor system requires a current of 400 mA at 24V dc from
the 1798-FTP sensor power connector for FLEX bus operation. This is
sufficient to support up to 8 modules. Remember to add this amount
to current requirements for other modules using the same 24V supply.
The FlexArmor system consumed 90 mA of DeviceNet power.

1798-0B4E

1798-BP4
4-position
Baseplate

FTP (Field Termination Plug)

1798-ADN

1798-N2