4 - troubleshooting, Chapter objectives, Troubleshoot with the indicators – Rockwell Automation 1798-IB4 FlexArmor User Manual User Manual

Page 51: Troubleshooting, Chapter

Advertising
background image

1

Publication 1798-UM001B-EN-P - November 2002

Chapter

4

Troubleshooting

Chapter Objectives

This chapter describes how to use the indicators on the module for
troubleshooting.

Troubleshoot With
the Indicators

Diagnostic indicators are located on the front of the adapter module.
They show both normal operation and error conditions in your
remote I/O system. The indicators are:

Mod/Net status

I/O status

The table below provides the indicator conditions and status.

Mod/Net Status Indicator

Indication

Status

Off

No power, or no network access

Flashing Green/OFF

On line, but not connected to master

Solid Green

On line, link OK, connected

Flashing Red

Recoverable fault

Solid Red

Critical adapter failure

I/O Status Indicator

Indication

Status

Off

No power or outputs off

Flashing Red/Off

Recoverable fault - outputs in fault

Flashing Green/Off

Idle/program mode - outputs in Idle

Solid Green

Device operational - outputs live - run

Solid Red

Critical adapter fault - unrecoverable

Advertising