Publication 1798-UM001B-EN-P - November 2002

Install Your DeviceNet Adapter Module 1-5

3. Repeat steps 1 and 2 for each I/O module for the remaining

Baseplate I/O slots.

4. Screw down the module retaining screws to ensure IP67

compliance.

Connect External Wiring

Connect external wiring to the DeviceNet Field Termination Plug
(DFTP) as shown below.

1. Connect the DeviceNet cable to the DFTP as shown.

2. Insert the connector into the mating connector on the

3. DeviceNet FTP module.

IMPORTANT

I/O modules can be installed in any slot location to
the right of the adapter module. The adapter is
capable of addressing eight modules.

IMPORTANT

Torque the screws to 0.5-0.7 Nm. (4.43-6.2 inch
pounds).

Dust caps on the I/O modules must have 4 inch
pounds of torque to maintain IP67 compliance.

Connect

Connector Pin

To

BLK Wire

3

-V

BLU Wire

5

CAN* Low

Base Wire

1

Drain

WHT Wire

4

CAN High

RED Wire

2

+V

*CAN=Controller Area Network