Install your flexarmor devicenet adapter module – Rockwell Automation 1798-IB4 FlexArmor User Manual User Manual

Page 12

Advertising
background image

Publication 1798-UM001B-EN-P - November 2002

1-4 Install Your DeviceNet Adapter Module

Set the Network
Address Switch on the
DeviceNet Adapter

Valid node addresses are 00 to 63.

Set the network address using the rotary switches. The setting of the
network address cannot be changed using the DeviceNet
configuration software.

Each module is shipped set for node address 63. The switches are
located on the underside of the module. The two switches are:

MSD (most significant digit)

LSD (least significant digit)

To reset the node address, use a small blade screwdriver to rotate the
switches. Line up the small black dot on the switch with the number
setting you wish to use.

Install Your FlexArmor
DeviceNet Adapter Module

To install the FlexArmor DeviceNet Adapter Module:

1. Hold the adapter at an angle and engage the top of the adapter

in the indention on the rear of the Baseplate.

2. Press the module down flush with the panel until the locking

lever locks.

IMPORTANT

The baud rate for the adapter is set by way of “baud
detection” (Autobaud) at power up.

MSD

LSD

Switches are
shown in the
63 position.

43387

IMPORTANT

The adapter module must be installed only in the
adapter slot, next to the FTP.

Advertising