2-2 How Communication Takes Place and I/O Image Table Mapping

For example, a 4 point discrete input module will have up to 2 read
words and 1 write word.

Check the I/O map for each module for the exact mapping.

About I/O Structure

Output data is received by the adapter in the order of the installed I/O
modules. The Output data for slot 0 is received first, followed by the
Output data for slot 1, and so on up to slot 7.

The first word of input data sent by the adapter is the Adapter Status
Word. This is followed by the input data from each slot, in the order
of the installed I/O modules. The Input data from slot 0 is first after
the status word, following by Input data from slot 2, and so on up to
slot 7.

4-point Discrete Input Module

I/O Image
Input Size

Output Size

1 or 2 Words

0 or 1 Words

Module Image

Inputs

Not used

Not used

Delay
Time

Delay
Time

...

...

...

...

...

DeviceNet Adapter

Network READ

Network WRITE

Read Data

Adapter Status

Slot 0 Input Data

Slot 1 Input Data

Slot 7 Input Data

Slot 0 Output Data

Slot 1 Output Data

Slot 7 Output Data

Read

Write

I/O Module
Slot 0

I/O Module
Slot 1

I/O Module
Slot 7