Mounting on the din rail – Rockwell Automation 1440-TB-H XM-947 Dynamic Vibration Terminal Base User Manual

Page 12

Advertising
background image

12 XM-947 Dynamic Vibration Terminal Base

Publication

GMSI10-IN027A-EN-P - May 2010

Mounting on the DIN Rail

You can also mount the terminal base to a grounded mounting plate. Refer to
the XM Module User Guide for details.

1. Position the terminal base unit on the 35 x 7.5mm DIN rail (A) (A-B

pt no. 199-DR1 or 199-DR4) at a slight angle.

2. Slide the terminal base unit over leaving room for the side

connector (B).

ATTENTION

The XM-947 makes a chassis ground connection through the DIN rail. Use zinc
plated, yellow chromated steel DIN rail to assure proper grounding. Using
other DIN rail materials (e.g. aluminum, plastic, etc.) which can corrode,
oxidize or are poor conductors can result in improper or intermittent platform
grounding.

Position terminal base at a slight angle and hook over the top of the DIN rail.

Advertising