XM-947 Dynamic Vibration Terminal Base 7

Publication

GMSI10-IN027A-EN-P - May 2010

Refer to the specifications for the specific module for power consumption
and other requirements.
See XM Power Supply Solutions application technique, publication
ICM-AP005A-EN-E, for additional details.

Interconnect Limit

Total current draw through the side connector cannot exceed 3A. A separate
power connection is necessary if the total current draw of the interconnecting
modules is greater than 3A.

Wiring Requirements

Use solid or stranded wire. All XM wiring should meet the following
specifications:

Output Power

100 Watts Maximum (~4A @ 24Vdc)

Static Regulation

± 2%

Dynamic Regulation

± 3%

Ripple

< 100mVpp

Output Noise

Per EN50081-1

Overshoot

< 3% at turn-on, < 2% at turn-off

Hold-up Time

As required (typically 50mS at full rated load

* When a fused supply is used the fuse must be a 5 amp, listed, fast acting fuse such as
provided by Allen-Bradley part number 1440-5AFUSEKIT.

TIP

If the total current draw for a row of modules is greater than 3A, consider
connecting power to a module near the center of the rail, rather than at a
module on either end. Insure that there is less than 3A load in either direction
from the module where power is connected.