16 XM-947 Dynamic Vibration Terminal Base

Publication

GMSI10-IN027A-EN-P - May 2010

13

Signal Common

39

Reserved

14

Signal Common

40

No Connection

15

Chassis

41

Chassis

16

No Connection

42

Chassis

17

No Connection

43

Chassis

18

No Connection

44

CAN_High (white wire)

19

Channel 1 Signal In

45

CAN_Low (blue wire)

20

Channel 1 Buffer Out

46

CAN Shield (bare wire)

21

Channel 2 Signal In

47

DeviceNet V (+) (red wire) (Optional,
see IMPORTANT note below)

22

Channel 2 Buffer Out

48

DeviceNet V (-) (black wire)

23

Channel 3 Signal In

49

No Connection

24

Channel 3 Buffer Out

50

No Connection

25

Channel 4 Signal In

51

No Connection

IMPORTANT

The DeviceNet power circuit through the XM module interconnect, which is
rated at only 300mA, is not intended or designed to power DeviceNet loads.
Doing so could damage the module or terminal base.

To preclude this possibility, even unintentionally, it is recommended that
DeviceNet V+ be left unconnected.