Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module User Manual

Page 14

Advertising
background image

14 XM Dynamic Measurement Module

Publication

ICM-IN002A-EN-P - March 2009

Network Status (NS)

Off

Module is not online.

• Module is autobauding.
• No power applied to the module;

look at Module Status LED.

Flashing Red

One or more I/O connections are in the
timed-out state.

Solid Red

Failed communications (duplicate MAC ID
or bus-off).

Flashing Green

Module is online but no connections are
currently established.

Solid Green

Module is online with connections
currently established.

Channel 0 &

Channel 1

Off

• Normal operation within alarm limits

on the channel.

• No power applied to the module; look

at the Module Status LED.

Solid Yellow

Alarm associated with this channel is in
Alert.

Solid Red

Alarm associated with this channel is in
Danger.

Flashing Red

A transducer fault exists on the channel.
DC bias is outside the DC Low and High
Limits.

Tachometer

Off

• Normal operation within alarm limits

on the channel.

• No power applied to the module; look

at the Module Status LED.

Solid Yellow

Alarm on Speed or Acceleration is in
Alert.

Solid Red

Alarm on Speed or Acceleration is in
Danger.

Indicator

State

Description