HS-3100/3200 Installation Manual

5

Note: Not to be used for ULC applications.

DACT Module - PID HS3DL

The optional Digital Alarm Communicator Transmitter
(DACT) module is added to the system to provide
Remote Station monitoring of system alarm, trouble,
and supervisory conditions.

Use of the DACT module requires that two telephone
lines be provided for connection to the DACT. Service
must be arranged with a Central Station monitoring
facility for Remote Station Service.

Refer to the HS3DL Installation Instructions for more
information.

HS3DL not to be used for ULC applications.

Reverse Polarity Municipal Box - PID HSCTYB

The optional HSCTYB can be configured for remote
Station (reverse polarity) or Municipal Master (local
energy) service. The HSCTYB can transmit alarm,
trouble, and supervisory conditions when configured for
reverse polarity operation. Alarm condition only is
reported when configured for Municipal Master
operation.

Refer to the HSCTYB Reverse Polarity Municipal Box
(RPMB) Module Installation Instructions
for more
information.

Compatible Products

HS-3644

The HS644 is a status annunciator with Liquid Crystal
Display, general system status lights, and general
function keys.

HS644 is not ULC Listed.

HS-3614

The MR-2614 is a status annunciator with LED zone
display, general system status lights, and general
function keys.