Notification appliance circuit connections, Function relay circuit connections – Harrington Signal HS-3200 - Install Manual User Manual

Page 24

Advertising
background image

HS-3100/3200 Installation Manual

18

Notification Appliance Circuit Connections

Class B (Style Y) NAC

This is a 2-wire Class B (Style Y) supervised signaling (notification appliance) circuit. Devices and
the 10k ohm end-of-line resister will be connected as indicated in the figure below. Maximum wire
lengths are shown in the Appendix. Use only approved devices.

Note:The appliances must incorporate a steering diode or other means of providing activation with
the alarm state and no current with the supervision state.

Class A (Style Z) Bell Circuit

This is a 4-wire Style Z (Class A) supervised signaling (notification appliance) circuit. Devices will
be connected as indicated in the diagram below. Maximum wire lengths are shown in the
Appendix. Distances noted therein account for the total length of wire, from the panel to furthest
device and back to the panel. Use only approved devices. Return wiring must be in a separate
conduit. The EOL is on the board for Class A applications.

Function Relay Circuit Connections

Form C programmable relays can only be connected to a Power Limited source limited to 2A @
30VDC. They have a power factor of 0.35.

10kΩ

EOLR

NAC2

MDR-EOL-10k

A+ A- B+ B- A+ A- B+ B-

NAC1

Circuit is supervised 24V FWR
power limited 2.0A MAX.

Figure 8: Class B NAC Wiring

NAC2

NAC1

A+ A- B+ B- A+ A- B+ B-

Circuit is supervised 24V FWR
power limited 2.0A MAX.

Figure 9: Class A NAC Wiring

Figure 10: Function Relay Wiring