4 applications & services, 5 general installation requirements, Manufacturer’s documents – Harrington Signal HS-3200 - Install Manual User Manual

Page 8: Field wiring, Compatible devices, 6 system verification, Standby power

Advertising
background image

HS-3100/3200 Installation Manual

2

1.4 Applications & Services

This fire alarm control panel is listed for use in the following applications:

Local with networking for UL (only) installations

Auxiliary (Requires HSCTYB Reverse Polarity Municipal Box Module configured for
Municipal Master Box Operation)

Central Station reporting (using the optional HSDL Dual Line Dialer-Communicator)

Remote Station reporting (Requires HSCTYB Reverse Polarity Municipal Box Module
configured for Reverse Polarity Operation or HSDL Dialer)

And for the following types of service:

M - Manual

A - Automatic

SS - Sprinkler Supervisory

WF - Waterflow

1.5 General Installation Requirements

The information provided with this unit is intended as a guide. Installation of this equipment,
optional system components, alarm initiating devices and notification appliances must follow the
manufacturer's guidelines as contained in their respective installation documents, all applicable
codes and the instructions of the Local Authority Having Jurisdiction.

Manufacturer’s Documents

When installing the fire alarm control panel, refer to this manual. When installing optional system
components refer to the installation documents included with those components. When installing
compatible alarm initiating devices or notification appliances, refer to the installation documents
included with those products.

Field Wiring

Field wiring recommendations in this document are intended as guidelines. All field wiring must be
installed in accordance with the applicable national electrical codes, with all relevant local codes
and standards, and the Local Authority Having Jurisdiction.

Compatible Devices

Use UL or ULC listed smoke detectors and notification devices that are compatible with the fire
alarm control panel from the lists included in this manual.

1.6 System Verification

The complete fire alarm system must be verified for proper installation and operation when:

The initial installation is ready for inspection by the Local Authority Having Jurisdiction;

Any system component is added, changed or deleted;

Any programming changes are made;

System wiring has been altered or repaired;

System failure due to the external influences such as lightning, water damage or extended
power outages has occurred.

Standby Power

The fire alarm control panel uses sealed lead-acid rechargeable batteries as a secondary power
source in the event of a main power failure. The required capacity of the standby batteries must be
calculated using the charts and tables within this manual for the period as required by national or
local codes and standards. Even though the calculation table within this manual includes a safety
margin, lead-acid batteries commonly used for standby can have variable capacity as a result of
age and ambient conditions. Periodic inspection for damage and the batteries' ability to support
the attached equipment is highly recommended.

Advertising