1.0 Technical Information

1.1 Introduction

The HS-3100/3200 Fire Alarm Control Panel (FACP) is the heart of a sophisticated
microprocessor based fire detection system. Meeting the demands of economy and capability,
these modular panel offer support for one or two loops of up to 198 devices on each loop.

Optional modules mount directly to the chassis. Modules are available that provide additional NAC
output circuits, function relay output circuits, annunciation, etc. This modular approach to system
design virtually guarantees that as your needs -- and applicable local codes -- evolve, your FACP
can change along with them.

Networking can be utilized to provide additional input circuits, visual zones, bell circuits and relays.
Up to 254 units (FACPs and/or annuciators) can be connected to form the Class A Style 7 (DCLR)
network loop.

Programming the HS3100/3200 has two components: Input circuit programming and special
features, such as day/night mode, et cetera, are done from an externally generated database
produced on a Windows based PC, while system parameters are programmed from the LCD and
keypad.

This manual covers the installation of the HS3100 and HS-3200 Fire Alarm Control Panels. For
Programming and Operating Instructions, please refer to the appropriate manuals.

1.2 Features

The HS-3100/3200 includes the following features:

HS-3100: One (1) Addressable Input (SLC) circuit, Class A (Style 6) or Class B (Style 4).

HS-3200: Two (2) Addressable Input (SLC) circuits, Class A (Style 6) or Class B (Style 4).

Two (2) Notification Appliance Circuits (NAC), Class A (Style Z) or Class B
(Style Y). Expandable to eight (8) NAC with optional module HSNC2 (groups of 2).

Four (4) Programmable function relays, Form C. Expandable to sixteen (16) relays with
optional module HSRL4 (groups of 4).

Two (2) Auxiliary power outputs.

Total 24V Power Supply: 2.6A, expandable to 8.2A.

Integral battery charger.

LCD/LED system status display, with optional LED zone display.

Surface/flush mount cabinet with dead-front construction, capable of holding two 12Ah
batteries with removable door for easy installation.

Removable terminal blocks for easy wiring.

Operating program and database can both be uploaded/downloaded by PC.

1.3 Codes & Standards

This fire alarm control panel meets the requirements of the following codes and standards:

NFPA 72 - National Fire Alarm Code, 1999 Edition

UL 864 Standard for Control Units for Fire Protective Signaling Systems

ULC-S527 Standard for Control Units for Fire Alarm Systems

Applicable Local and State Building Codes

NFPA 70 - National Electric Code

ULC-S524 Installation of Fire Alarm Systems